Overview
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
The Darkroom model has two cowls, the interior cowl being designed to give light protection. It can be installed in windows, partitions, external walls or roofs. Extended fixing rods for fixing thicknesses up to 370mm are supplied with the unit. Provision should be made for adequate air replacement through Vent-Axia non-vision grilles. For areas requiring total light exclusion, contact your local Vent-Axia Sales Office.
Model Range
|
|
| TX6DR |
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
|
|
|
|
|
|
| TL6DR |
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
|
|
|
|
|
|
| TX7DR |
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
|
|
|
|
|
|
| TL7DR |
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
|
|
|
|
|
|
| TX9DR |
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
|
|
|
|
|
|
| TL9DR |
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
|
|
|
|
|
|
| TX12DR |
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
|
|
|
|
|
|
| TL12DR |
A range designed for photographic, medical, dental and veterinarian applications - used also for opticians and other specialist applications. Most darkrooms need a minimum of ten air changes per hour for comfort and efficiency. For rooms containing heat producing equipment (eg: print glazers) a higher rate of air change may be desirable.
|
|
|
|
[^Top of page]Accessories
|
|
| Ecotronic 130 Controller |
All the features of T-Series:-
* Infinitely variable speed control
* 'E' position for energy saving
* Minimum speed adjustment.
|
|
|
|
|
|
| Ecotronic 400 Controller |
For groups of units of any one size up to a total of 400 watts. Do not mix T-Series with Standard Range ventilating units on one controller.
|
|
|
|
|
|
| Ambient Response Humidity Sensor |
The latest self programming electronic On/Off wall mounted humidity sensor which reacts to any rapid increase in humidity and temperature by switching a Vent-Axia fan ‘On’ for rapid removal of moisture laden air, in domestic bathrooms and kitchens. Can be wired into controller "Auto" mode connections. Night time RH increment setback feature suppresses uisance tripping when the humidity level gradually rises as the temperature falls.
Features & Benefits:
- Ambient operating temp range +5°C to +40°C.
- Changeover relay switch.
|
|
|
|
|
|
| Air Quality Sensor |
Automatically reacts to the depletion of air quality, sensing tobacco smoke, smells and toilet odours to regulate mechanically ventilated areas such as cinemas, pubs, clubs, restaurants, kitchens, toilets and conference rooms.
|
|
|
|
|
|
| Ecotronic Humidity Sensor |
An adjustable set point, solid state On/Off sensor. A pullcord provides manual override, indicated by lamp. Adjustable from 65 to 90%RH. Can be wired into controller "Auto" mode connections. Incorporates changeover switch to select low/high speed.
Features & Benefits:
- Ambient operating temp range 0°C to +40°C.
- BEAB Approved.
- Dimensions: 87 x 87 x 33mm (H x W x D).
- Maximum switching load 1 amp inductive.
- Pullcord override indicated by lamp.
- Setting Range: 65% - 90%RH.
|
|
|
|
[^Top of page]Product Specification
Shutter
With energy savings in mind TX models are supplied complete with an integral instantaneous automatic louvre shutter concealed behind the interior cowl. Operates on intake and extract at any angle of mounting.
The shutter is electronically controlled by an actuator with a damped action giving quiet operation during instant opening and closing. The interlocking edges of the shutter blades provide maximum backdraught protection.
When used with a T-Series controller, the shutter can be set open with the fan motor switched Off to provide natural ventilation without the security risk of an open window.
TL models do not have a shutter. They are suitable for room to room systems and where there is a need for ventilation of specialised equipment. The TL model will also provide natural ventilation where required when the unit is switched Off. Suitable for operation in ambient temperatures from -40°C to +50°C.
Electrical
Suitable for running at any angle. Quiet running, enclosed. Fitted with self resetting Standard Thermal Overload Protection (S.T.O.P.).
Supply voltage: 220-240V/1/50Hz (120V/1/60 Hz).
| Unit size | | 6 | |
| Type | | TX6DR | TL6DR |
| Stock Ref. No. | | W16 12 10 | W26 12 10 |
| Amps @ 240V | | 0.24 | 0.21 |
| Extract Performance m³/h | Low | 200 | |
| Extract Performance m³/h | Med | 240 | |
| Extract Performance m³/h | High | 265 | |
| Watts (high) | | 45 | 40 |
| dB(A) (med) @ 3m | | 43 | |
| Shutter (TX only) Instant |
| Surface Controllers | T-Series Type TSC | W36 11 19 | |
| Surface Controllers | Ecotronic 130 | W30 01 20 | |
| Surface Controllers | Ecotronic 400 | W36 23 20 | |
| Surface Controllers | Time Switch TTC | W36 13 10 | |
| Unit size | | 7 | |
| Type | | TX7DR | TL7DR |
| Stock Ref. No. | | W16 22 10 | W26 22 10 |
| Amps @ 240V | | 0.24 | 0.21 |
| Extract Performance m³/h | Low | 330 | |
| Extract Performance m³/h | Med | 415 | |
| Extract Performance m³/h | High | 530 | |
| Watts (high) | | 46 | 41 |
| dB(A) (med) @ 3m | | 2 | |
| Shutter (TX only) | | Instant | |
| Surface Controllers T-Series | Type TSC | W36 11 19 | |
| Surface Controllers T-Series | Ecotronic 130 | W30 01 20 | |
| Surface Controllers T-Series | Ecotronic 400 | W36 23 20 | |
| Surface Controllers T-Series | Time Switch TTC | W36 13 10 | |
| Unit size | | 9 | |
| Type | | TX9DR | TL9DR |
| Stock Ref. No. | | W16 32 10 | W26 32 10 |
| Amps @ 240V | | 0.42 | 0.39 |
| Extract Performance m³/h | Low | 455 | |
| Extract Performance m³/h | Med | 630 | |
| Extract Performance m³/h | High | 725 | |
| Watts (high) | | 80 | 75 |
| dB(A) (med) @ 3m | | 42 | |
| Shutter (TX only) | | Instant | |
| Surface Controllers | T-Series Type TSC | W36 11 19 | |
| Surface Controllers | Ecotronic 130 | W30 01 20 | |
| Surface Controllers | Ecotronic 400 | W36 23 20 | |
| Surface Controllers | Time Switch TTC | W36 13 10 | |
| Unit size | | 12 | |
| Type | | TX12DR | TL12DR |
| Stock Ref. No. | | W16 42 10 | W26 42 10 |
| Amps @ 240V | | 0.51 | 0.48 |
| Extract Performance m³/h | Low | 870 | |
| Extract Performance m³/h | Med | 1040 | |
| Extract Performance m³/h | High | 1130 | |
| Watts (high) | | 105 | 100 |
| dB(A) (med) @ 3m | | 42 | |
| Shutter (TX only) | | Instant | |
| Surface Controllers | T-Series Type TSC | W36 11 19 | |
| Surface Controllers | Ecotronic 130 | W30 01 20 | |
| Surface Controllers | Ecotronic 400 | W36 23 20 | |
| Surface Controllers | Time Switch TTC | W36 13 10 | |
| Flush box Stock Ref. No. 40 01 44 |
[^Top of page]Performance

[^Top of page]Dimensions
| Size | 6 (150mm) | 7 (190mm) | 9 (230mm) | 12 (300mm) |
| A | 100 | 136 | 136 | 171 |
| B | 196 | 206 | 229 | 308 |
| C | 285 | 400 | 400 | 500 |
| D | 220 | 258 | 302 | 378 |
| E | 226 | 265 | 304 | 381 |
| F | 19 | 19 | 19 | 19 |
| Fixing Hole Diameter | 184 | 222 | 260 | 337 |
| Weight (kg) | 4.13 | 5.33 | 6.60 | 10.05 |

[^Top of page]Typical Specifications
Supply and install a T-Series Darkroom fan as manufactured by Vent-Axia Ltd, Fleming Way, Crawley, West Sussex, RH10 9YX Telephone: 01293526062.
The fan should be able to give a minimum of 10 air changes per hour, it should have two cowls to give light protection while mounted in windows partitions, external walls and roofs. The fan should be able to extract through walls up to 370mm thick by use of extended fixing rods.
The fan should have a speed control pack which enables high, medium and low speed to be set to suit room size or required duty.
The fan should be fully reversible and be able to be controlled by using variable speed controllers or by humidity, air quality or PIR sensors.
The fan should incorporate an electronically controlled instantaneous shutter mechanism that has a facility to be in an open state without the fan running for passive ventilation.
The unit should meet with Document F of the Building Regulations and be BEAB approved.
The motor should be suitable to run at any angle and suitable for operation in ambient temperatures from -40°C to +50°C and should be fitted with self resetting Standard Thermal Overload Protection (S.T.O.P.).
Patented Shutter Actuator System
European Patent Number EP 0177215
Patented Remote Speed Control Circuit
European Patent Number EP 0180311.