Overview
Super T-Series 355, 400, 450 and 500mm fans are efficient, quiet power with performances up to 4940m³/h. Tough heavy duty internal grilles and external weather shutters ensure the longevity, performance and the peace of mind.
Model Range
|
| Super T ST355-16-WL |
Super T - Gravity shutters
Extract model incorporating gravity shutter and internal grille.
When installed only the room side aluminium fascia grille is visible. The outside is finished with an external gravity shutter and frame.
|
|
|
|
|
| Super T TX |
Extract or intake models with a powerful 6 pole fan. Quiet smooth operation electric shutters provide controllability and are suitable for exposed installations.
|
|
|
|
|
| Super T GF |
Super T GF, with grease filter. Delivered complete with a powerful 4 pole fan, matching Grease Filter housing and tray kit. Comprises stainless steel housing and 50mm stainless steel framed mesh filter. Spare filters can be supplied in packs of two.
|
|
|
|
|
| Super T AR and ARX |
Super T AR and ARX Air makeup units. High capacity EU4 pleated filter, which fits inside the wall liner (non powered). AR units have a fixed heavy duty external louvre, ARX have an electric shutter.
|
|
|
|
|
| Super T ST450-16-WL |
Super T - Gravity shutters
When installed only the room side aluminium fascia grille is visible. The outside is finished with an external gravity shutter and frame.
|
|
|
|
|
| Super T ST355-16-WL |
Super T - Gravity shutters
Extract model incorporating gravity shutter and internal grille.
When installed only the room side aluminium fascia grille is visible. The outside is finished with an external gravity shutter and frame.
|
|
|
|
|
| Super T ST500-16-WL |
Super T - Gravity shutters
When installed only the room side aluminium fascia grille is visible. The outside is finished with an external gravity shutter and frame.
|
|
|
|
[^Top of page]Accessories
|
|
| 2.5Amp Electronic Controller |
Performance can be selected using an electronic controller.
Surface mounting
Provides infinitely variable speed control and features an On/Off/sensor slider with neon indicator. Adjustable minimum speed setting. Electrical connections for use with suitable external sensors are provided.
86 x 156 x 53mm (HxWxD).
Hole for wall box:
80 x 150 x 50mm (H x W x D).
|
|
|
|
|
|
| Thermo Switch |
Automatically switches on fans on either a rise or fall in air temperature. Can be used for Trickle/ Boost operation on
either intake or extract systems. Setting range: +6°C to +30°C. Two internal range limit/locking rings are included to allow setting within a limited temperature range or locking at a fixed set-point. IP20 rated. Sealed sensing mechanism. Mounting direct on surface only. Dimensions: 80 x 104 x 36mm (H x W x D).
|
|
|
|
|
|
| 7 Day TimeSwitch |
For applications where regular switching is required at fixed periods or at different times on different days of the week, eg: offices, shops, pubs and restaurants.
The 7-day TimeSwitch gives twelve On or Off positions per day and can be set for 7 days. The cycle will repeat until changed.
Features & Benefits:
- Ambient operating temp range -20°C to +85°C.
- Analogue clock display and integral time switches for ease of setting.
- Dimensions: 104 x 74 x 52mm (H x W x D).
- Manual override.
|
|
|
|
|
|
| Guardian Personnel Detector (PIR Sensor) |
Suitable for controlling a range of Vent-Axia fans. Continuously monitors an area and activates when a moving body is detected.
Features & Benefits:
- Adjustable timer overrun (5 seconds to 20 minutes).
- Ambient operating temp range -20°C to +50°C.
- Designed to meet IP44.
- Internal use only.
- Maximum load: 10 amp resistive (5 amp inductive). Suitable for use with fluorescent lighting up to 500W.
|
|
|
|
|
|
| Super Grease Filter |
Super T; GR (Grease Filter) Dimensions (mm)
Impeller dia. 355 400
A 552 640
B 520 622
C 390 440
D 100 100
E 364 420
F 520 622
G 436 486
H 81 70
|
|
|
|
[^Top of page]Product Specification
Construction & Impellers
The axial fan at the heart of the Super T range is based on an integrated impeller and internal rotor motor design which produces a very compact unit. A specially designed bellmouth inlet and mounting plate, ensures an excellent performance to sound level ratio. The mounting plate is formed from a single sheet material protected with a tough epoxy finish.
Motor supports are manufactured from steel rod. Manufacture is controlled to BS EN ISO 9001 standards.
Impellers are moulded in glass filled polyamide for resistance to harsh conditions and abrasive airflow.
Electrical
Single phase 220-240V 50Hz. Capacitor start and run. An IP65 terminal box is supplied with all models with conduit entry from the side of the wall liner. All motors are fitted with Standard Thermal Overload Protection (S.T.O.P.), which should be wired via the controller.
| Type | 355-16 | 400-16 | 450-16 | 500-16 | 355-14 | 400-14 |
| Extract Perf (m³/h) | 1735 | 2165 | 3550 | 4940 | 3057 | 4523 |
| Watts | 94 | 110 | 225 | 295 | 203 | 340 |
| S.C. Amps | 1.25 | 1.4 | 2.58 | 4.0 | 2.40 | 4.10 |
| F.L.C. Amps | 0.5 | 0.56 | 1.15 | 1.6 | 0.96 | 1.64 |
| dB(A) @ 3m | 40 | 45 | 48 | 51 | 56 | 59 |
[^Top of page]Dimensions
| Impeller dia. | 355 | 400 | 450 | 500 |
| A | 550 | 597 | 657 | 727 |
| B | 550 | 597 | 657 | 727 |
| C | 470 | 520 | 580 | 650 |
| D | 470 | 520 | 580 | 650 |
| Weight (kg) | 17 | 22 | 28 | 33 |
| Impeller dia. | 355 | 400 |
| A | 552 | 640 |
| B | 520 | 622 |
| C | 390 | 440 |
| D | 100 | 100 |
| E | 364 | 420 |
| F | 520 | 622 |
| G | 436 | 486 |
| H | 81 | 70 |


Super T; GR (Grease Filter) Dimensions (mm)

Super T GF - Typical Installation:

[^Top of page]Typical Specifications
Supply and install a Super T-Series fan as manufactured by Vent-Axia Ltd, Fleming Way, Crawley, West Sussex, RH10 9YX, Telephone: 01293 526062.
The fan should have a telescopic sleeve for wall thicknesses between 280 and 312mm. The fan should be protected to a market leading IP65 and designed for ambient air temperatures up to +70°C and should come complete with internal grilles and external weather shutters.
The unit should have specially designed bellmouth plate, integrated impeller and internal rotor motor. The motor ball bearings should be greased for life. Rotors are dynamically balanced to ISO 1940.
The motor insulation should be Class F with operating temperatures from -40 to +70°C and should be fitted with self resetting Standard Thermal Overload Protection (S.T.O.P.).
[^Top of page]