Overview
A versatile and robust range of roof extract ventilating units designed to satisfy the requirements of efficient ventilation in commercial and industrial applications. The simple, proven design of Standard range makes installation and routine cleaning easy.
Featuring a low profile cowl, the unit is ready for fitting into horizontal, angled and vertical glass, fixing plates on roofs and in vertical windows or walls in exposed areas. With Vent-Axia roof plate assemblies, all four sizes can be fitted easily into flat roofs. Suitable for roof installation plus window and wall installation in exposed areas (eg: coastal positions).
Vent-Axia's spigot and ring method of fixing ensures easy installation and weather proof joint. We recommend the use of sealing compound under the upper part of the unit when fitted in roofs.
Easy Cleaning
Integrated component design allows all parts to be dismantled for cleaning without the use of specialist tools.
Model Range
|
|
| Standard Range Roof Model S7RF |
Classic Retro-Styled Ventilation
A versatile and robust range of roof extract
ventilating units designed to satisfy the
requirements of efficient ventilation in
commercial and industrial applications. The
simple, proven design of Standard Range
makes installation and routine cleaning
easy
|
|
|
|
|
|
| Standard Range Roof Model S6RF |
Classic Retro-Styled Ventilation
A versatile and robust range of roof extract
ventilating units designed to satisfy the
requirements of efficient ventilation in
commercial and industrial applications. The
simple, proven design of Standard Range
makes installation and routine cleaning
easy.
|
|
|
|
|
|
| Standard Range Roof Model S9RF |
Classic Retro-Styled Ventilation
A versatile and robust range of roof extract
ventilating units designed to satisfy the
requirements of efficient ventilation in
commercial and industrial applications. The
simple, proven design of Standard Range
makes installation and routine cleaning
easy.
|
|
|
|
|
|
| Standard Range Roof Model S12RF |
Classic Retro-Styled Ventilation
A versatile and robust range of roof extract
ventilating units designed to satisfy the
requirements of efficient ventilation in
commercial and industrial applications. The
simple, proven design of Standard Range
makes installation and routine cleaning
easy.
|
|
|
|
[^Top of page]Accessories
|
|
| Ecotronic Controller |
For groups of units of any one size up to a total of 400 watts. Do not mix T-Series with Standard Range ventilating units on one controller.
|
|
|
|
|
|
| Ambient Response Humidity Sensor |
The latest self programming electronic On/Off wall mounted humidity sensor which reacts to any rapid increase in humidity and temperature by switching a Vent-Axia fan ‘On’ for rapid removal of moisture laden air, in domestic bathrooms and kitchens. Can be wired into controller "Auto" mode connections. Night time RH increment setback feature suppresses uisance tripping when the humidity level gradually rises as the temperature falls.
Features & Benefits:
- Ambient operating temp range +5°C to +40°C.
- Changeover relay switch.
|
|
|
|
|
|
| Air Quality Sensor |
Automatically reacts to the depletion of air quality, sensing tobacco smoke, smells and toilet odours to regulate mechanically ventilated areas such as cinemas, pubs, clubs, restaurants, kitchens, toilets and conference rooms.
|
|
|
|
|
|
| Ecotronic Humidity Sensor |
An adjustable set point, solid state On/Off sensor. A pullcord provides manual override, indicated by lamp. Adjustable from 65 to 90%RH. Can be wired into controller "Auto" mode connections. Incorporates changeover switch to select low/high speed.
Features & Benefits:
- Ambient operating temp range 0°C to +40°C.
- BEAB Approved.
- Dimensions: 87 x 87 x 33mm (H x W x D).
- Maximum switching load 1 amp inductive.
- Pullcord override indicated by lamp.
- Setting Range: 65% - 90%RH.
|
|
|
|
[^Top of page]Product Specification
Motor
Purpose designed enclosed motor. Suitable for running at any angle. Quiet running, continuous rated motor with sealed for life ball bearings.
Suitable for operation in ambient temperatures from -40°C to +50°C.
Fitted with Standard Thermal Overload Protection. (S.T.O.P.)
Supply voltage 220-240V/1/50Hz.
Installation
All Standard Range roof models are designed to fit directly into horizontal and sloping windows including wired cast, up to 10mm thick.
In solid roofs, install using a roof plate assembly and, if required, and eggcrate grille in the ceiling below. A suitable sealing compound should be used between the glass/roofplate and the exterior seal.
| Unit size | 6 | 7 | 9 | 12 |
| Type | S6/RF | S7/RF | S9/RF | S12/RF |
| Stock Ref. No. | 13 14 10 | 13 24 10 | 13 34 10 | 13 44 10 |
| Amps @ 240V | 0.16 | 0.16 | 0.24 | 0.36 |
| Extract Perf MAX m³/h | 240 | 350 | 625 | 1130 |
| Watts MAX. | 32 | 34 | 53 | 84 |
| dB(A) (med) @ 3m | 36 | 31 | 39 | 42 |
| Shutter Type SD/R | 23 17 10 | 23 27 10 | 23 37 10 | 23 47 10 |
| Range-master | | | | |
| RVS Surface | W30 01 10 | W30 01 10 | W30 01 10 | W30 01 10 |
| Flush Fitting | W30 01 10 | W30 01 10 | W30 01 10 | W30 01 10 |
| + 40 01 44 | + 40 01 44 | + 40 01 44 | + 40 01 44 |
| Time Switch Type | W36 13 10 | W36 13 10 | W36 13 10 | W36 13 10 |
| Multi-unit Type MUC | W36 23 10 | W36 23 10 | W36 23 10 | W36 23 10 |


[^Top of page]Dimensions
| Impeller dia. | 150mm | 190mm | 230mm | 300mm |
| A | 140 | 147 | 166 | 201 |
| BØ | 216 | 254 | 295 | 381 |
| C | 21 | 21 | 21 | 21 |
| D | 95 | 108 | 121 | 146 |
| EØ | 267 | 330 | 394 | 508 |
| Fixing hole dia. | 184 | 222 | 260 | 337 |
| Weight 3.2kg | 3.9kg | 5.5kg | 8.5kg |
| Size | A | B | C |
| 6 | 300 mm | 335 mm | 475 mm |
| 7 | 300 mm | 335 mm | 475 mm |
| 9 | 450 mm | 490 mm | 630 mm |
| 12 | 450 mm | 490 mm | 630 mm |


[^Top of page]Typical Specifications
Supply and install a Standard Range Roof fan as manufactured by Vent-Axia Ltd, Fleming Way, Crawley, West Sussex, RH10 9YX, Telephone: 01293 526062.
The fan should be fully extract only and be able to be controlled by using variable speed controllers or by humidity, air quality or TimeSwitches.
The fan should feature a low profile cowl and should be suitable for horizontal, angled and vertical glass.
The unit should meet with Document F of the Building Regulations. DEMKO Approved.
The motor should be suitable for mounting at any angle and suitable for operation in ambient temperatures from -40°C to +40°C and should be fitted with self resetting Standard Thermal Overload Protection (S.T.O.P.).
[^Top of page]