The Sentinel Twin in-line duct fans are as supplied from Vent-Axia Ltd. Manufactured from prime quality galvanised sheet steel, Sentinel fan units are internally treated with an ‘O’ class rated, BS476 part 6 & 7, acoustic foam, which offers the benefits of high soundabsorption, good thermal insulation properties in addition to self extinguishing properties and resistant to ignition.
The housing is designed to be as compact as possible for concealed false ceiling applications and Sentinel casings re specially designed to allow the unit to be mounted via its unique mounting bracket, ensuring a quick and easy solution to installation.
The unit is suitable for ceiling or floor mounting, non-return dampers can be easily rotated on site to suit.


All Sentinel units feature a low energy, Class 1, EC/DC external rotor motor and backward curved impeller assembly specifically chosen for performance and nonoverloading characteristics. The assembly is dynamically balanced to DIN ISO 1940 Grade 6.3, motor size 500mm rated IP54, all other sizes, IP44 according to BS EN 60529. Ball bearings are greased for life. Insulation is Class 'B' (from -25°C to +60°C).
All models incorporate internal electronic overload protection and soft start function.

Every Sentinel unit is fitted with a purpose designed common PCB controller incorporating a 16-character backlit alphanumerical x 2 line display with 4 button membrane keypad for fan status and commissioning set up. The enclosure is fitted with a 4-pole 10A isolator that is suitable for fitting a locking device to prevent accidental operation.
Motors are single phase 230V +/- 10% / 50/60Hz / 1ph (size 100-400mm) or 400V +/- 10% / 50/60Hz / 3ph (size 500mm), (4 wire systems only).
The twin unit controller features automatic 6hr duty/share and run/standby in the event of motor failure.
24V DC power is provided from the controller for powering the matched range of Sentinel switches and sensors.

Extensively tested to BS848 parts 1 & 2. Published dB(A) figures are free field sound pressure levels at 3m with spherical propagation at reference level of 2 x 10-5 Pa. The inlet/outlet sound power level spectra figures are dB with a reference of 10–12 watts.

Ordering Codes are similar to existing units with Suffix.... /WP which denotes Weatherproof finish.
Example: SENT100T/CP/WP



Hierarchy Model
| Constant Pressure Model
| Dimensions in mm(*)
| Weight Kg
|
| a
| b
| c
| d
| e
| f
| g
|
| 100T
| 100T/CP
| 610
| 705
| 100
| 591
| 717
| 256
| 622
| 26
|
| 125T | 125T/CP | 610 | 705 | 125 | 591 | 717
| 256 | 622 | 26
|
| 150T | 150T/CP | 610 | 705 | 150 | 591 | 717
| 256 | 622 | 26
|
| 200T | 200T/CP | 801 | 896 | 200 | 703 | 830
| 343 | 734 | 39
|
| 250T | 250T/CP | 925 | 1020 | 250 | 798 | 925
| 354 | 829 | 48
|
| 315T | 315T/CP | 1255 | 1353 | 315 | 1145 | 1272
| 536 | 1176 | 88
|
| 400T | 400T/CP | 1255 | 1353 | 400 | 1145 | 1272
| 536 | 1176 | 90
|
| 500T | 500T/CP | 1492 | 1590 | 500 | 1533 | 1661
| 675 | 1564 | 175
|
|